HONEYWELL 8C-TAOXB1 51307137-175 Analog Output Module
Function:
Configurable Safe-State Behaviors (FAILOPT): Each channel's behavior in the event of a failure can be configured individually.
FAILOPT (Fail-Safe Options):
SHED TO A SAFE VALUE: Transition to a predefined safe value (e.g., zero) in the event of a failure.
Parameter
Specification
Input / Output Module
8C-TAOXB1 51307137-175
Output Type
4-20 mA
Output Channels
16
Output Ripple
100 mV peak-to-peak at power line frequency, across250 Ω load
Load Resistance
50-800Ω
Voltage Rating
24 VDC
Module current rating
190 mA
Resolution
± 0.05% of Full Scale
Module Removal and InsertionUnder Power
Supported
Calibrated Accuracy
± 0.2% of Full Scale (25oC) including linearity
Directly Settable Output Current Range
2.9 mA to 21.1 mA
Maximum Open Circuit Voltage
22 V